Fan Coil Units
Fan coil units for domestic and commercial hydronic systems — 2-pipe 8-way cassettes, ultra-thin EC motor ducted units and 130 mm super-slim consoles, with matching installation parts.
Specifications
| Parameter | Value |
|---|---|
| Unit types | 2-pipe 8-way cassette · ultra-thin EC motor ducted FCU · 130 mm super-slim console |
| Cassette heating output | 14.5–18.9 kW at 60°C |
| Cassette air distribution | 8-way, 3D |
| Ducted unit | 19 cm high · 530–1750 m³/h · sound from 37 dB · EC or AC motor option |
| Console | 130 mm deep · 5-speed DC motor, 200–2000 rpm · 34–39 dB |
| Modes | Cooling, heating and dehumidification |
| Controls | Wired or remote controller, Wi-Fi option; LCD thermostat on the ducted unit |
| Cassette filter and drain pan | Removable washable filter; drain pan moulded in high-density polystyrene |
| Installation parts | Electric 2-way / 3-way / 4-way valves, ball valves, Y-type ball valve with filter, flexible joints, external drain pump, insulated condensate pipe |
Values as published in the 2026 product catalogue. Ask us for the model-level submittal sheet before specifying.
Features
- ✓Three unit types for domestic and commercial projects: a 2-pipe 8-way cassette, an ultra-thin EC motor ducted unit, and a 130 mm super-slim console
- ✓Cassette delivers 14.5–18.9 kW of heating at 60°C, with 8-way 3D air distribution
- ✓Removable, washable filter and a drain pan moulded in high-density polystyrene on the cassette
- ✓Ducted unit is 19 cm high, with 530–1750 m³/h air flow and sound levels from 37 dB
- ✓Console is 130 mm deep, with a 5-speed DC motor (200–2000 rpm) and 34–39 dB operation
- ✓Cooling, heating and dehumidification, with EC or AC motor options
- ✓Wired or remote control with a Wi-Fi option; LCD thermostat on the ducted unit
- ✓Matching installation parts: electric two-way, three-way and four-way valves, brass ball valves, a Y-type ball valve with filter, brass and stainless steel flexible joints, an external drain pump for fan coils, and condensate pipe with an insulation layer
Overview
A fan coil unit is the indoor terminal of a hydronic system: water from the heat pump or chiller passes through the coil, and the fan moves room air across it. The three units here cover the usual ways a room gets built — a 2-pipe 8-way cassette for open ceilings, an ultra-thin EC motor ducted unit for concealed installation, and a 130 mm super-slim console for perimeter wall or floor mounting.
The three types are specified for different constraints rather than different duties. The cassette delivers 14.5–18.9 kW of heating at a 60°C flow temperature with 8-way 3D air distribution. The ducted unit is 19 cm high, with 530–1750 m³/h of air flow and sound levels from 37 dB. The console is 130 mm deep, with a 5-speed DC motor between 200 and 2000 rpm and 34–39 dB operation. All three cool, heat and dehumidify, and take a wired or remote controller with a Wi-Fi option.
Because the units are the visible half of a hydronic system, the installation parts are usually specified with them: electric two-way, three-way and four-way valves, ball valves, a Y-type ball valve with filter, brass and stainless steel flexible joints, an external drain pump for fan coils, and condensate pipe with an insulation layer. Specifying them together keeps valve and joint sizes matched to the coil connections.
Where it is used
- Room-by-room heating and cooling on air-to-water heat pump systems, in domestic and light commercial projects
- Cassette units where a single ceiling position has to cover an open space with 8-way air distribution
- Ultra-thin ducted units where the ceiling void is shallow and a 19 cm unit height is the limiting dimension
- Super-slim consoles on perimeter walls or floors where a 130 mm depth is what fits
- Projects that take the installation parts from the same supplier — valves, flexible joints, drain pump and condensate pipe
Selection & installation notes
- 01
Choose the unit type by how the room is built: cassette for open ceilings, ducted for concealed installation, console for perimeter wall or floor mounting.
- 02
Check the heating output against the room load at the flow temperature your system runs — the published cassette figure is quoted at 60°C.
- 03
Match the valves and flexible joints to the coil connections. The parts listed for this range run from DN15/20 to DN20.
- 04
Confirm coil connections and control options per model on the submittal sheet; the exact configuration depends on the unit selected.
Common questions
What unit types are available?
Three: a 2-pipe 8-way cassette (14.5–18.9 kW at 60°C heating), an ultra-thin EC motor ducted unit (19 cm high, 530–1750 m³/h) and a 130 mm super-slim console (5-speed DC motor, 200–2000 rpm).
Do these units work with air-to-water heat pumps?
Yes. A fan coil unit is the indoor terminal of a hydronic circuit, so it takes the water loop from the heat pump or chiller and transfers it to room air. The range covers cooling, heating and dehumidification.
Which installation parts are supplied with them?
Electric two-way, three-way and four-way valves (2-wire, DN15/20 and DN20), brass ball valves, a Y-type ball valve with filter, brass and stainless steel flexible joints (30 cm, DN20), an external drain pump for fan coils, and condensate pipe with an insulation layer. An accessories package bundles the common combination.
What controls and maintenance features are there?
Wired or remote controllers with a Wi-Fi option; the ducted unit is supplied with an LCD thermostat. The cassette has a removable, washable filter and a drain pan moulded in high-density polystyrene.
Read more on this topic
Related products
Furnaces
Gas furnaces for dual-fuel and add-on heat pump configurations, 2–5 ton.
R290 Heat Pumps — European Market Localisation
R290 (propane) heat pumps localised for European market requirements — refrigerant, voltage, documentation and certification to local specification.
Titanium Heat Exchanger