The water side of a heat pump gets less attention than the refrigerant side, which is a mistake with a predictable bill attached. Refrigerant circuits are sealed at the factory by people who do it for a living. Water circuits are assembled on site, filled with whatever the local supply provides, and then left alone for a decade.
That is the environment in which magnetite forms.
What magnetite is and where it comes from
Magnetite is black iron oxide — Fe₃O₄, the mixed-valence oxide that forms when steel meets water in the presence of oxygen. In a closed hydronic system there are three inputs:
- Oxygen, introduced with the initial fill and again with every top-up of make-up water. A system that needs frequent topping up is a system that is continuously being fed the raw material for corrosion.
- Steel, in radiators, pipework, pumps, expansion vessels and any mild-steel component in the loop.
- Heat, which accelerates the reaction. The hottest surfaces in the loop corrode first.
The resulting particles are fine, dark and magnetic. They do not stay suspended indefinitely.
Why it ends up in the heat pump
Magnetite leaves the water where velocity is low and where the flow path changes direction. In a heat pump system, the component that satisfies both conditions is the heat exchanger.
Brazed plate heat exchangers — the common choice for the water side of a monobloc or split hydronic heat pump — have narrow channels and a large number of direction changes by design, because that is how they achieve high heat transfer in a small package. The same geometry that makes them efficient makes them a settling zone.
The consequences arrive in a recognisable order:
- Rising pressure drop. Deposits narrow the channels. The pump has to work harder to move the same flow, and the flow the system actually delivers falls.
- Falling heat transfer. An insulating layer of oxide on the plate surface separates the refrigerant from the water it is supposed to be heating. Capacity and efficiency both suffer, and the control system compensates by running longer or hotter.
- Faults and trips. Flow switches, differential pressure switches and high-limit protections begin to nuisance-trip. At this stage the complaint is usually “the heat pump is unreliable”, not “the water is dirty”.
- Mechanical damage. Magnetite is abrasive. It collects in pump volutes and wears seals, and it deposits in valve bodies and three-port valves, which then fail to seat.
None of these failures announce themselves with a water sample. They arrive as a service history.
What a magnetic filter does — and what it does not
A magnetic filter is a collection device with two capture mechanisms in one body:
- A magnet, which holds the magnetic fraction: the magnetite itself. The units we build use either a 12,000 gauss magnet in a 22/28 mm body with 3/4″–1¼″ connections, or a 6,000 gauss magnet in a 22 mm G3/4 body.
- A mesh strainer, which holds the non-magnetic fraction: scale fragments, solder debris, sand and general suspended solids. The compact unit uses a wear-resistant 16-mesh stainless steel element.
That combination is why a magnetic filter is not the same product as a strainer, and not the same product as a chemical inhibitor. It is worth being explicit about the division of labour:
| Measure | What it does | What it does not do |
|---|---|---|
| Magnetic filter | Removes magnetic and non-magnetic particulate from the circulating water | Does not remove dissolved oxygen, and does not stop corrosion |
| Corrosion inhibitor | Passivates metal surfaces and buffers water chemistry | Does not remove particulate that has already formed |
| Fill water treatment | Reduces the oxygen and hardness entering the loop | Does not address what is already in the system |
| Air separation | Removes entrained air, one of the corrosion inputs | Does not capture solid oxide |
A filter buys you time and protects the heat exchanger. It does not replace water treatment, and any specification that presents it as a substitute is selling a service problem forward.
Sizing and placement
The pressure and temperature envelope matters more than the gauss figure on the box. Our two bodies are rated as follows, and both numbers have to be checked against the loop:
| Compact unit | Standard unit | |
|---|---|---|
| Magnet | 6,000 gauss | 12,000 gauss |
| Connection | 22 mm, G3/4 | 22/28 mm, 3/4″–1¼″ |
| Max working pressure | 4 bar | 5 bar |
| Max working temperature | 90 °C | with high-temperature EPDM seals |
| Max flow | — | 50 L/min |
Placement rules that matter in practice:
- Full flow, return side, upstream of the heat pump. A filter on a bypass cleans a fraction of the water and leaves the heat exchanger exposed to the rest.
- Isolation valves on both sides. If the filter cannot be serviced without draining the loop, it will not be serviced.
- Check the seal material against the loop temperature. High-temperature EPDM is the specification to ask for on the standard body.
- Account for glycol. A glycol loop has different viscosity and flow characteristics. Size the filter for the flow you actually have, not the water-only figure.
- Vertical or horizontal, but with the magnet accessible. Service access decides whether the device works long-term.
The maintenance reality
A magnetic filter is the only component in this discussion whose effectiveness depends entirely on somebody opening it.
- At commissioning, record the pressure drop across the filter with a clean element. That number is your baseline for every future service visit.
- Check the magnet and the mesh after the first heating season. In a retrofit onto an existing system, the first season mobilises deposits that have been sitting in the pipework for years, and the captured volume will be higher than in any later year.
- Thereafter, service on a fixed interval tied to the site, and always log the pressure drop.
- Clean the mesh; do not just wipe the magnet. The magnetic fraction is the visible one, and the strainer is doing half the work.
The failure mode to watch for is a filter that has become a flow restriction because it filled up and nobody looked. That converts a protective device into a performance problem, and it is the most common way this component earns a bad reputation.
What to put in the submittal
For the filter: connection size and type, magnet strength, mesh rating, maximum flow, maximum working pressure and temperature, seal material, service method, and whether isolation valves are included. For the system: fill water quality, inhibitor specification, air separation method, and the commissioning pressure drop across the filter.
Our magnetic filter page lists both bodies with their ratings and connections. The heat pumps these filters are usually protecting are described on the R-290 heat pump and modular air-to-water pages, and the rest of the hydronic parts range — mixing centres, manifolds, actuators and valves — is indexed on the products overview. For how the water side sits inside a complete system design, the heat pump solutions hub is the place to start.