Air outlets are the cheapest line in the mechanical schedule and the first thing an occupant notices. That combination explains most of the complaints: the outlets get selected last, from a catalogue page, on the basis of what fits the ceiling, and the room is then judged by how the air behaves.
The selection is not difficult, but it is specific. Every outlet type can be made to work; the differences appear in throw, noise, draught and what happens when the system switches from cooling to heating.
What actually differs between the types
Air outlets are not interchangeable because they do not project air the same way. The geometry decides the throw pattern, the induction (how quickly supply air mixes with room air), and the noise generated at a given flow.
| Type | How it projects air | Usually selected for | What to check |
|---|---|---|---|
| Jet diffuser | Long, adjustable throw from a nozzle | Atria, airports, tall spaces where supply must reach across a long distance | Throw at the design flow, and whether the nozzle can be aimed after installation |
| Slot diffuser | Long continuous linear throw, low noise | Continuous architectural lines, curtain-wall perimeters, offices | Number of slots and the plenum arrangement; continuity of the line |
| Swirl diffuser | Radial discharge with high induction | Variable-volume systems; spaces that also heat | Heating-mode behaviour, and draught at minimum flow |
| Round ceiling diffuser | Multi-cone radial pattern | Suspended ceilings, general commercial rooms | Neck size versus face size, and the pattern control ring |
| Square ceiling diffuser | Multi-cone, square face | Standard 600 × 600 ceiling grids | Grid module fit and border width |
| Linear bar grille | Directional, bar-deflected | Sills, perimeters, return air | Bar spacing and deflection setting |
| Single deflection grille | Adjustable in one axis | Wall supply where air must be aimed left/right or up/down | Which axis is adjustable |
| Double deflection grille | Adjustable in both axes | Wall supply where the pattern must be aimed in two directions | Blade rigidity once set, and access for adjustment |
| Return grille | Low velocity intake | Return air paths | Pressure drop and generated noise — throw is not the issue |
| Eggcrate grille | Very open face, minimal deflection | High-volume returns, and supply where low pressure drop matters | Free area and filter/access coordination |
| Door grille / transfer grille | Non-vision transfer path | Pressure equalisation between rooms | Acoustic rating of the partition it penetrates |
| Gravity louver | Opens with airflow, closes when stopped | Exhaust or intake where backdraft protection is wanted without a motor | Blade sealing and the pressure required to open |
| Weather louver | Exterior intake/exhaust with rain defence | Outdoor air intakes and exhausts | Face velocity, drainable blades, and the water carryover limit |
| Air disc valve | Circular valve with a rotating disc | Volume control and extract in low-velocity systems | Leakage class, pressure drop, and whether it is also doing the balancing |
| Baseboard grille | Low-level distribution | Residential perimeter supply or return | Size against the wall run — our plastic baseboard grille is offered in 16 × 8 and 26 × 8 |
Two of those rows are not air-distribution selections at all, and it is worth separating them out: a door grille is a pressure-relief device whose main constraint is the acoustic rating of the wall it penetrates, and an air disc valve is a control device whose main constraint is leakage and pressure drop. Selecting either one on appearance is how balancing problems start.
The four numbers to demand
For any outlet you intend to specify, four numbers decide whether the selection is finished. If a supplier cannot provide them for the specific size at your design flow, the selection is not finished — it is a guess with a part number attached.
- Throw at a stated terminal velocity. Throw is meaningless without the terminal velocity it is measured to — commonly quoted at 0.25 m/s (50 fpm) or 0.5 m/s. Ask which one, and ask for the isothermal condition, because buoyancy changes the answer.
- Pressure drop at the design flow. This is what the fan has to overcome, and it belongs in the duct calculation. A grille chosen for appearance and left out of the pressure budget shows up as a deficient flow at commissioning.
- Sound power or NC contribution at the design flow. Noise varies steeply with velocity. An outlet that is quiet at half flow can be the loudest thing in the room at design flow. Note the test condition, including any damper position.
- Free area, for returns and for any outlet where the face velocity matters.
Where those numbers come from matters as much as the numbers. Air outlet performance is measured under a recognised test method rather than asserted: ASHRAE Standard 70 is the method of testing the performance of air outlets and air inlets, and ratings published against it come with test conditions attached — including the plenum arrangement and the damper position. Ask for the rating basis and the test condition, not just the figure. A throw number with no stated test method is not a specification.
Heating mode is where ceiling selections fail
A ceiling outlet selected on cooling performance can behave badly in heating, and the reason is buoyancy. Warm supply air is lighter than room air, so it resists the downward projection the outlet was selected for. The result is a warm layer at the ceiling and a cold floor — the classic “the heat pump is running but the room is cold” complaint.
Practical consequences:
- Ask for heating-mode throw data, not only cooling. If it does not exist, treat the selection as unverified.
- High-induction outlets (swirl patterns in particular) generally mix supply air into room air faster, which shortens the distance over which buoyancy can dominate.
- Perimeter and low-level supply puts warm air where the heat loss is, which is why baseboard and sill arrangements persist in heating-dominated markets.
- For variable-volume systems, check minimum flow: draught complaints usually come from the low end, not the design point.
For the comfort side, the criteria that matter are the ones in ASHRAE Standard 55 — air speed and temperature in the occupied zone, and the local discomfort limits. Draught is a comfort failure, and it is a selection failure.
Health Canada’s guidance on ventilation makes the same point from the health side: ventilation air has to be distributed to the occupied rooms, which is a duct-and-outlet design question rather than an equipment question. A correctly sized ventilator that delivers its air to one end of the house has not solved the problem it was installed for. The same guidance is useful when commissioning, because it describes how to measure air movement and thermal comfort rather than assuming them.
Return air, transfer air and the paths people forget
Return and transfer paths are where a good supply design gets undone. Three points are worth building into the schedule:
- Size returns for low pressure drop and low noise. They are not projection devices; a return selected like a supply (small face, high velocity) whistles.
- Provide transfer paths deliberately. A room with a closed door and no transfer grille will find its own path — through the door undercut, or through the building envelope. Undercuts are a legitimate path, but they should be sized, not discovered.
- Transfer paths carry sound. A door grille or transfer duct passes noise between rooms as readily as it passes air. Where the partition has an acoustic requirement, the transfer path is part of that requirement.
Also worth separating in the specification: fire and smoke dampers are not air outlets. They are regulated life-safety products with their own listings and installation requirements, and they belong on a different part of the schedule from the diffuser they sit behind.
What to put in the submittal
An air outlet submittal that clears review carries:
- Type and pattern (including whether the pattern is adjustable, and in which axes);
- Neck size and face size — they are not the same number, and the duct connects to the neck;
- Material and finish, and the ceiling or wall interface detail (border, grid module, plaster frame);
- Free area, and the filter arrangement where the outlet includes one;
- Throw at the design flow with the terminal velocity stated, plus the heating-mode figure;
- Pressure drop and sound power / NC at the design flow;
- Access: how the outlet or the volume damper behind it is reached for balancing and cleaning;
- Where applicable, the balancing device and its leakage class — and whether the outlet itself is the balancing device.
Then check it against the room: does the throw reach the occupied zone without landing on people, does the return path exist, and does the pressure budget still balance with the outlet pressure drops included?
Our diffuser and grille range lists the outlet types and sizes we build, including air disc valves and the plastic baseboard grille in 16 × 8 and 26 × 8. Outlets are only one end of the system: the ventilation solutions hub covers how supply, extract and ducting fit together, the indoor air quality hub puts filtration and dehumidification in the same picture, and for the duct side of the same design the PIR pre-insulated duct guide covers the choice between panel and galvanised ductwork. Where a ducted fan is doing the moving, the EC inline duct fan range is the relevant starting point.